Skip to main content

AquaForce® Variable Speed Air-Cooled Screw Chiller
30XV

with R-134a Refrigerant

140 to 500 Nominal Tons

The Carrier® AquaForce® 30XV air-cooled variable-speed screw chiller was developed to ensure the best performance and efficiency in a solution that’s easy to install, easy to service, highly reliable and quiet. The 30XV delivers with industry leading efficiency (IPLV Ratings greater than 21.0 available in certain models) and sound.  The smaller footprint 30XV can replace just about all older equipment going back two generations. The 30XV can be customized to fit most building needs, anywhere.

Now Available with Waterside Economizer

The addition of a waterside economizer allows the chiller to use an auxiliary source of chilled water rather than the compressor and mechanical coils, which can optimize performance and reduce down time due to environmental challenges such as cold weather.

Air-cooled chillers within the scope of the ACCL certification program are certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Performance Features

  • Full-load EER values above 11.0 and IPLV values above 21.0
  • Tiered approach providing from the smallest footprint to the best in class efficiency 
  • ASHRAE 90.1-2013 compliant / AHRI certified
  • Operation from -20 F to 125 F ambient conditions
  • High-efficiency variable speed screw compressors
  • Standard uncoated or optional e-coated Novation® micro channel heat exchanger (MCHX) condenser coils (factory-installed option)
  • Standard 25kA SCCR rating for all voltages (Except 575V, 10kA)

Additional Important Options

  • Al/Cu, Cu/Cu Condenser Coils
  • Multiple Sound Configurations 
  • High SCCR factory installed 
  • Variable Speed Condenser Fans 
  • Capacity Recover under 4 mins
  • BACnet Translator (factory-installed option) or BACnet and LON translator control (factory-installed option or field-installed accessory)
  • Optional Energy Management Module minimizes chiller energy consumption (factory-installed option or field-installed accessory)    

Reliability Features

  • ASME constructed evaporators / ETL (and ETL Canada) listed
  • Heavy-gage galvanized steel frame
  • Coil Trim Panels, Security grilles and Full Hail guards/Privacy screen choices (factory-installed option or field-installed accessory)
  • Low ambient head pressure control (factory-installed option or field-installed accessory)
  • Coil corrosion coatings available on all coil types (factory-installed option)

Maintenance Features

  • Over 15 diagnostic functions & trending capability 
  • Permanently lubricated fan motor bearings
  • Compressor suction service valves (factory-installed option)
  • Microchannel condenser coils with inherent corrosion resistance and offering simplified cleaning (factory-installed option)
  • Unit-mounted, non-fused disconnect (factory-installed option)
  • Remote service port for easier machine diagnostics (factory-installed option or field-installed accessory) 

Installation Features

  • Factory charged with R-134a refrigerant
  • GFI (ground fault interrupter) convenience outlet (factory-installed option or field-installed accessory)
  • Remote evaporator kit (field-installed accessory)
  • Single or dual-point electrical connections available (factory-installed option)
  • Control transformer (factory-installed option)
  • Structurally robust base

Standard Warranty

  • One year from start-up or 18 months from shipment limited warranty
  • 3-year coil parts warranty on Novation micro channel heat exchanger
  • Extended warranty packages available up to 10 years 

Factory-Installed Options

  • Low-Sound
  • Sound Optimization
  • Condenser Coil Options
  • E-Coated Micro Channel
    • Al/Cu Fins 
    • Pre-coated Al/Cu Fins
    • Cu/Cu Coils
    • E-Coated Al/Cu Coils
    • E-Coated Cu/Cu Coils 
  • Isolation Valve
  • Suction Line Insulation
  • Energy Management Module (EMM) + GFI
  • Chilled Water Temperature Reset (via 4-20 mA Signal; EMM Required)
  • Demand Limit (via 4-20 mA signal, 2 addition steps; EMM Required)
  • Variable Speed Condenser Fans
  • BACnet Translator (MS/TP)
  • LONworks Translator
  • Dual Point Primary Power Entry 
  • Control Transformer
  • Unit Mounted Main Disconnect, Non-fused
  • High SCCR
  • Condenser Coil Trim Panels
  • Security Grilles
  • Hail Guards
  • Full Hail Guards
  • Skid & Bag

Field-Installed Accessory Kits

  • Energy Management Module (EMM) & GFI
  • Chilled Water Temperature Reset (via 4-20 mA signal; EMM Required)
  • Demand Limit
  • LONworks Translator
  • Dual Chiller Accessory Kit 
  • Condenser Coil Trim Panels
  • Security Grilles
  • Full Hail Guard

30XV Weights & Dimensions

Size Weight (lb) Weight (kg) Length (in) Length (mm) Width (in) Width (mm) Height (in) Height (mm)
140 S 11110 5039 206 5226 88 2236 99 2513
140 M 11175 5069 206 5226 88 2236 99 2513
140 H 12058 5469 253 6420 88 2236 99 2513
160 S 11175 5069 206 5226 88 2236 99 2513
160 M 12245 5554 253 6420 88 2236 99 2513
160 H 13112 5948 300 7614 88 2236 99 2513
180 S 11362 5154 206 5226 88 2236 99 2513
180 M 12317 5587 253 6420 88 2236 99 2513
180 H 13184 5980 300 7614 88 2236 99 2513
200 S 12317 5587 253 6420 88 2236 99 2513
200 M 13413 6084 300 7614 88 2236 99 2513
200 H 14202 6442 347 8808 88 2236 99 2513
225 S 13185 5981 253 6420 88 2236 99 2513
225 M 14108 6399 300 7614 88 2236 99 2513
225 H 14975 6793 347 8808 88 2236 99 2513
250 S 15415 6992 300 7614 88 2236 99 2513
250 M 16566 7514 347 8808 88 2236 99 2513
250 H 17614 7989 394 10002 88 2236 99 2513
275 S 15864 7196 300 7614 88 2236 99 2513
275 M 16624 7541 347 8808 88 2236 99 2513
275 H 17492 7934 394 10002 88 2236 99 2513
300 S 16624 7541 347 8808 88 2236 99 2513
300 M 17560 7965 394 10002 88 2236 99 2513
300 H 18401 8346 441 11196 88 2236 99 2513
325 S 17560 7965 394 10002 88 2236 99 2513
325 M 18478 8381 441 11196 88 2236 99 2513
325 H 19407 8803 488 12390 88 2236 99 2513
350 S 20672 9377 406 10304 88 2236 99 2513
350 M 22326 10127 453 11498 88 2236 99 2513
350 H 23104 10480 500 12692 88 2236 99 2513
400 S 23760 10777 453 11498 88 2236 99 2513
400 M 24729 11217 500 12692 88 2236 99 2513
400 H 25507 11570 547 13886 88 2236 99 2513
450 S 24729 11217 500 12692 88 2236 99 2513
450 M 26356 11955 547 13886 88 2236 99 2513
450 H 27221 12347 594 15080 88 2236 99 2513
500 S 26356 11955 547 13886 88 2236 99 2513
500 M 27337 12400 594 15080 88 2236 99 2513

Notes

1) Indicated weight is for chiller employing MCHX condenser coils and standard (2-pass) evaporator.
2) For 2-piece shipment module weights, see the current product data.

Performance Features

  • Full-load EER values above 11.0 and IPLV values above 21.0
  • Tiered approach providing from the smallest footprint to the best in class efficiency 
  • ASHRAE 90.1-2013 compliant / AHRI certified
  • Operation from -20 F to 125 F ambient conditions
  • High-efficiency variable speed screw compressors
  • Standard uncoated or optional e-coated Novation® micro channel heat exchanger (MCHX) condenser coils (factory-installed option)
  • Standard 25kA SCCR rating for all voltages (Except 575V, 10kA)

Additional Important Options

  • Al/Cu, Cu/Cu Condenser Coils
  • Multiple Sound Configurations 
  • High SCCR factory installed 
  • Variable Speed Condenser Fans 
  • Capacity Recover under 4 mins
  • BACnet Translator (factory-installed option) or BACnet and LON translator control (factory-installed option or field-installed accessory)
  • Optional Energy Management Module minimizes chiller energy consumption (factory-installed option or field-installed accessory)    

Reliability Features

  • ASME constructed evaporators / ETL (and ETL Canada) listed
  • Heavy-gage galvanized steel frame
  • Coil Trim Panels, Security grilles and Full Hail guards/Privacy screen choices (factory-installed option or field-installed accessory)
  • Low ambient head pressure control (factory-installed option or field-installed accessory)
  • Coil corrosion coatings available on all coil types (factory-installed option)

Maintenance Features

  • Over 15 diagnostic functions & trending capability 
  • Permanently lubricated fan motor bearings
  • Compressor suction service valves (factory-installed option)
  • Microchannel condenser coils with inherent corrosion resistance and offering simplified cleaning (factory-installed option)
  • Unit-mounted, non-fused disconnect (factory-installed option)
  • Remote service port for easier machine diagnostics (factory-installed option or field-installed accessory) 

Installation Features

  • Factory charged with R-134a refrigerant
  • GFI (ground fault interrupter) convenience outlet (factory-installed option or field-installed accessory)
  • Remote evaporator kit (field-installed accessory)
  • Single or dual-point electrical connections available (factory-installed option)
  • Control transformer (factory-installed option)
  • Structurally robust base

Standard Warranty

  • One year from start-up or 18 months from shipment limited warranty
  • 3-year coil parts warranty on Novation micro channel heat exchanger
  • Extended warranty packages available up to 10 years 

Factory-Installed Options

  • Low-Sound
  • Sound Optimization
  • Condenser Coil Options
  • E-Coated Micro Channel
    • Al/Cu Fins 
    • Pre-coated Al/Cu Fins
    • Cu/Cu Coils
    • E-Coated Al/Cu Coils
    • E-Coated Cu/Cu Coils 
  • Isolation Valve
  • Suction Line Insulation
  • Energy Management Module (EMM) + GFI
  • Chilled Water Temperature Reset (via 4-20 mA Signal; EMM Required)
  • Demand Limit (via 4-20 mA signal, 2 addition steps; EMM Required)
  • Variable Speed Condenser Fans
  • BACnet Translator (MS/TP)
  • LONworks Translator
  • Dual Point Primary Power Entry 
  • Control Transformer
  • Unit Mounted Main Disconnect, Non-fused
  • High SCCR
  • Condenser Coil Trim Panels
  • Security Grilles
  • Hail Guards
  • Full Hail Guards
  • Skid & Bag

Field-Installed Accessory Kits

  • Energy Management Module (EMM) & GFI
  • Chilled Water Temperature Reset (via 4-20 mA signal; EMM Required)
  • Demand Limit
  • LONworks Translator
  • Dual Chiller Accessory Kit 
  • Condenser Coil Trim Panels
  • Security Grilles
  • Full Hail Guard

30XV Weights & Dimensions

Size Weight (lb) Weight (kg) Length (in) Length (mm) Width (in) Width (mm) Height (in) Height (mm)
140 S 11110 5039 206 5226 88 2236 99 2513
140 M 11175 5069 206 5226 88 2236 99 2513
140 H 12058 5469 253 6420 88 2236 99 2513
160 S 11175 5069 206 5226 88 2236 99 2513
160 M 12245 5554 253 6420 88 2236 99 2513
160 H 13112 5948 300 7614 88 2236 99 2513
180 S 11362 5154 206 5226 88 2236 99 2513
180 M 12317 5587 253 6420 88 2236 99 2513
180 H 13184 5980 300 7614 88 2236 99 2513
200 S 12317 5587 253 6420 88 2236 99 2513
200 M 13413 6084 300 7614 88 2236 99 2513
200 H 14202 6442 347 8808 88 2236 99 2513
225 S 13185 5981 253 6420 88 2236 99 2513
225 M 14108 6399 300 7614 88 2236 99 2513
225 H 14975 6793 347 8808 88 2236 99 2513
250 S 15415 6992 300 7614 88 2236 99 2513
250 M 16566 7514 347 8808 88 2236 99 2513
250 H 17614 7989 394 10002 88 2236 99 2513
275 S 15864 7196 300 7614 88 2236 99 2513
275 M 16624 7541 347 8808 88 2236 99 2513
275 H 17492 7934 394 10002 88 2236 99 2513
300 S 16624 7541 347 8808 88 2236 99 2513
300 M 17560 7965 394 10002 88 2236 99 2513
300 H 18401 8346 441 11196 88 2236 99 2513
325 S 17560 7965 394 10002 88 2236 99 2513
325 M 18478 8381 441 11196 88 2236 99 2513
325 H 19407 8803 488 12390 88 2236 99 2513
350 S 20672 9377 406 10304 88 2236 99 2513
350 M 22326 10127 453 11498 88 2236 99 2513
350 H 23104 10480 500 12692 88 2236 99 2513
400 S 23760 10777 453 11498 88 2236 99 2513
400 M 24729 11217 500 12692 88 2236 99 2513
400 H 25507 11570 547 13886 88 2236 99 2513
450 S 24729 11217 500 12692 88 2236 99 2513
450 M 26356 11955 547 13886 88 2236 99 2513
450 H 27221 12347 594 15080 88 2236 99 2513
500 S 26356 11955 547 13886 88 2236 99 2513
500 M 27337 12400 594 15080 88 2236 99 2513

Notes

1) Indicated weight is for chiller employing MCHX condenser coils and standard (2-pass) evaporator.
2) For 2-piece shipment module weights, see the current product data.