i-Vu® Lightning Protection Board
PROT485
Network Device
Carrier's ancillary network devices ensure optimum performance for BACnet MS/TP and other EIA-485 networks. These devices install easily and work together to amplify data signals and provide surge protection, bias and termination to any EIA-485 network.
Key Features & Benefits
The PROT485 provides electrical surge protection to controllers installed within 250ft. (76m)
Power
|
n/a |
Mounting | 4" Snap Track
|
Terminals | Removable screw terminals
|
Network Requirement | At each place wire enters or exits the building, or for maximum protection, 1 recommended within 250 ft. (76m) of each controller.
|
Network Wiring | 22/24 AWG, single twisted shielded pair, low capacitance, CL2P wire
|
Protection | 2 replaceable 0.5 A fuses protect the Fused connection:
F1, type 3AG, 250 Vac, 0.5 A, T (time-lag) F2, type 3AG, 250 Vac, 0.5 A, T (time-lag) |
Operating Temperature | -20° to 140°F (-29° to 60°C), 10-90% relative humidity, non-condensing |
Listed by | UL-916 (PAZX), cUL-916 (PAZX7), CE EN50082-1997
|
Dimensions | 4" (width) by 4" (height) by 2" (depth) / 102mm (width) by 102mm (height) by 51mm (depth) |
Key Features & Benefits
The PROT485 provides electrical surge protection to controllers installed within 250ft. (76m)
Power
|
n/a |
Mounting | 4" Snap Track
|
Terminals | Removable screw terminals
|
Network Requirement | At each place wire enters or exits the building, or for maximum protection, 1 recommended within 250 ft. (76m) of each controller.
|
Network Wiring | 22/24 AWG, single twisted shielded pair, low capacitance, CL2P wire
|
Protection | 2 replaceable 0.5 A fuses protect the Fused connection:
F1, type 3AG, 250 Vac, 0.5 A, T (time-lag) F2, type 3AG, 250 Vac, 0.5 A, T (time-lag) |
Operating Temperature | -20° to 140°F (-29° to 60°C), 10-90% relative humidity, non-condensing |
Listed by | UL-916 (PAZX), cUL-916 (PAZX7), CE EN50082-1997
|
Dimensions | 4" (width) by 4" (height) by 2" (depth) / 102mm (width) by 102mm (height) by 51mm (depth) |
California residents please see Proposition 65