i-Vu® XT BACnet® Link
XT-LB
Network & Integration Device
The i-Vu® XT BACnet link allows you to integrate other manufacturers’ equipment into the i-Vu® building automation system using the BACnet protocol, making it easy to tie in equipment such as VFDs, boilers, and lighting systems. Each i-Vu® XT BACnet link supports up to 1,500 third party BACnet points.
The i-Vu® XT BACnet link also routes BACnet messages between the i-Vu® building automation system backbone (BACnet/IP), and a subnetwork of i-Vu® controllers (BACnet MS/TP and/or BACnet ARCnet). It connects directly to the Ethernet LAN and provides the i-Vu® web server with access to the entire i-Vu system.
The i-Vu® XT BACnet link also extends an i-Vu® system, allowing individual BACnet MS/TP networks (with up to 60 controllers each), and BACnet ARCnet networks (with up to 99 controllers each), to be connected together via the i-Vu® building automation system backbone.
BACnet Support | Conforms to the BACnet Building Controller (B-BC), BACnet Router (B-RTR), and BACnet BBMD (B-BBMD) device profiles as defined in BACnet 135-2012 Annex L, Protocol Revision 14 |
Power Requirements | 24VAC ± 10%, 50-60Hz, 50 VA
26VDC ± 10%, 15W |
Communication Ports | Gig-E: 10/100/1000 BaseT Ethernet port for BACnet/IP, BACnet/Ethernet and/or Modbus/IP networks
S1 MSTP: High-speed EIA-485 port for connecting one of the following network types: BACnet MS/TP or Modbus RTU network at 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps S2 MSTP: Electrically isolated EIA-485 port for connecting BACnet MS/TP or Modbus RTU network at 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps S1 and S2 End of Net switch can be turned on to terminate the network segment Local Access: 10/100 Base T Ethernet port for system start-up and troubleshooting |
Protection | Device is protected by a replaceable, fast acting, 250Vac, 2A, 5mm x 20mm glass fuse. The power and network ports comply with the EMC requirements EN50491-5-2. |
Integration | Maximum 1500 third-party BACnet points (BACnet/IP, BACnet MS/TP, or BACnet ARCnet)
Maximum 500 client or server Modbus points (Modbus/IP, Modbus RTU) Maximum 999 control programs or available memory |
Real-Time Clock | Real-time clock keeps track of time in the event of a power failure for up to 3 days. |
LED Status Indicators | Tricolor NET LED to show network status / Tricolor SYS LED to show system status
A TX (Transmit) and RX (Receive) LED for: Gig-E port, Port S1, Port S2 |
Router Addressing | Rotary DIP switches set address of router |
Environmental Operating Range | Operating: 0 to 140ºF (-18 to 60ºC); 10 to 90% RH, non-condensing
Storage: -24 to 140ºF (-30 to 60ºC); 10 to 90% RH, non-condensing |
Compliance | United States of America: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL listed to UL916, PAZX, Energy Management Equipment Canada: Industry Canada Compliant, ICES-003, Class A; cUL listed UL 916, PAZX and Energy Management Equipment Europe: CE mark, EN50491-5-2:2009 , Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment; EN50491-3: 2009, Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS); Low Voltage Directive: 2006/95/EC; RoHS Compliant: 2011/65/EU Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3; |
Physical | Fire-retardant plastic ABS, UL94-5VA |
BACnet Support | Conforms to the BACnet Building Controller (B-BC), BACnet Router (B-RTR), and BACnet BBMD (B-BBMD) device profiles as defined in BACnet 135-2012 Annex L, Protocol Revision 14 |
Power Requirements | 24VAC ± 10%, 50-60Hz, 50 VA
26VDC ± 10%, 15W |
Communication Ports | Gig-E: 10/100/1000 BaseT Ethernet port for BACnet/IP, BACnet/Ethernet and/or Modbus/IP networks
S1 MSTP: High-speed EIA-485 port for connecting one of the following network types: BACnet MS/TP or Modbus RTU network at 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps S2 MSTP: Electrically isolated EIA-485 port for connecting BACnet MS/TP or Modbus RTU network at 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps S1 and S2 End of Net switch can be turned on to terminate the network segment Local Access: 10/100 Base T Ethernet port for system start-up and troubleshooting |
Protection | Device is protected by a replaceable, fast acting, 250Vac, 2A, 5mm x 20mm glass fuse. The power and network ports comply with the EMC requirements EN50491-5-2. |
Integration | Maximum 1500 third-party BACnet points (BACnet/IP, BACnet MS/TP, or BACnet ARCnet)
Maximum 500 client or server Modbus points (Modbus/IP, Modbus RTU) Maximum 999 control programs or available memory |
Real-Time Clock | Real-time clock keeps track of time in the event of a power failure for up to 3 days. |
LED Status Indicators | Tricolor NET LED to show network status / Tricolor SYS LED to show system status
A TX (Transmit) and RX (Receive) LED for: Gig-E port, Port S1, Port S2 |
Router Addressing | Rotary DIP switches set address of router |
Environmental Operating Range | Operating: 0 to 140ºF (-18 to 60ºC); 10 to 90% RH, non-condensing
Storage: -24 to 140ºF (-30 to 60ºC); 10 to 90% RH, non-condensing |
Compliance | United States of America: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL listed to UL916, PAZX, Energy Management Equipment Canada: Industry Canada Compliant, ICES-003, Class A; cUL listed UL 916, PAZX and Energy Management Equipment Europe: CE mark, EN50491-5-2:2009 , Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment; EN50491-3: 2009, Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS); Low Voltage Directive: 2006/95/EC; RoHS Compliant: 2011/65/EU Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3; |
Physical | Fire-retardant plastic ABS, UL94-5VA |
BACnet Support | Conforms to the BACnet Building Controller (B-BC), BACnet Router (B-RTR), and BACnet BBMD (B-BBMD) device profiles as defined in BACnet 135-2012 Annex L, Protocol Revision 14 |
Power Requirements | 24VAC ± 10%, 50-60Hz, 50 VA
26VDC ± 10%, 15W |
Communication Ports | Gig-E: 10/100/1000 BaseT Ethernet port for BACnet/IP, BACnet/Ethernet and/or Modbus/IP networks
S1 MSTP: High-speed EIA-485 port for connecting one of the following network types: BACnet MS/TP or Modbus RTU network at 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps S2 MSTP: Electrically isolated EIA-485 port for connecting BACnet MS/TP or Modbus RTU network at 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps S1 and S2 End of Net switch can be turned on to terminate the network segment Local Access: 10/100 Base T Ethernet port for system start-up and troubleshooting |
Protection | Device is protected by a replaceable, fast acting, 250Vac, 2A, 5mm x 20mm glass fuse. The power and network ports comply with the EMC requirements EN50491-5-2. |
Integration | Maximum 1500 third-party BACnet points (BACnet/IP, BACnet MS/TP, or BACnet ARCnet)
Maximum 500 client or server Modbus points (Modbus/IP, Modbus RTU) Maximum 999 control programs or available memory |
Real-Time Clock | Real-time clock keeps track of time in the event of a power failure for up to 3 days. |
LED Status Indicators | Tricolor NET LED to show network status / Tricolor SYS LED to show system status
A TX (Transmit) and RX (Receive) LED for: Gig-E port, Port S1, Port S2 |
Router Addressing | Rotary DIP switches set address of router |
Environmental Operating Range | Operating: 0 to 140ºF (-18 to 60ºC); 10 to 90% RH, non-condensing
Storage: -24 to 140ºF (-30 to 60ºC); 10 to 90% RH, non-condensing |
Compliance | United States of America: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL listed to UL916, PAZX, Energy Management Equipment Canada: Industry Canada Compliant, ICES-003, Class A; cUL listed UL 916, PAZX and Energy Management Equipment Europe: CE mark, EN50491-5-2:2009 , Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment; EN50491-3: 2009, Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS); Low Voltage Directive: 2006/95/EC; RoHS Compliant: 2011/65/EU Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3; |
Physical | Fire-retardant plastic ABS, UL94-5VA |
BACnet Support | Conforms to the BACnet Building Controller (B-BC), BACnet Router (B-RTR), and BACnet BBMD (B-BBMD) device profiles as defined in BACnet 135-2012 Annex L, Protocol Revision 14 |
Power Requirements | 24VAC ± 10%, 50-60Hz, 50 VA
26VDC ± 10%, 15W |
Communication Ports | Gig-E: 10/100/1000 BaseT Ethernet port for BACnet/IP, BACnet/Ethernet and/or Modbus/IP networks
S1 MSTP: High-speed EIA-485 port for connecting one of the following network types: BACnet MS/TP or Modbus RTU network at 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps S2 MSTP: Electrically isolated EIA-485 port for connecting BACnet MS/TP or Modbus RTU network at 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps S1 and S2 End of Net switch can be turned on to terminate the network segment Local Access: 10/100 Base T Ethernet port for system start-up and troubleshooting |
Protection | Device is protected by a replaceable, fast acting, 250Vac, 2A, 5mm x 20mm glass fuse. The power and network ports comply with the EMC requirements EN50491-5-2. |
Integration | Maximum 1500 third-party BACnet points (BACnet/IP, BACnet MS/TP, or BACnet ARCnet)
Maximum 500 client or server Modbus points (Modbus/IP, Modbus RTU) Maximum 999 control programs or available memory |
Real-Time Clock | Real-time clock keeps track of time in the event of a power failure for up to 3 days. |
LED Status Indicators | Tricolor NET LED to show network status / Tricolor SYS LED to show system status
A TX (Transmit) and RX (Receive) LED for: Gig-E port, Port S1, Port S2 |
Router Addressing | Rotary DIP switches set address of router |
Environmental Operating Range | Operating: 0 to 140ºF (-18 to 60ºC); 10 to 90% RH, non-condensing
Storage: -24 to 140ºF (-30 to 60ºC); 10 to 90% RH, non-condensing |
Compliance | United States of America: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL listed to UL916, PAZX, Energy Management Equipment Canada: Industry Canada Compliant, ICES-003, Class A; cUL listed UL 916, PAZX and Energy Management Equipment Europe: CE mark, EN50491-5-2:2009 , Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment; EN50491-3: 2009, Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS); Low Voltage Directive: 2006/95/EC; RoHS Compliant: 2011/65/EU Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3; |
Physical | Fire-retardant plastic ABS, UL94-5VA |