33CNTRAN485-01-R

Product Integrated Controller

Controller provides ability to integrate Carrier Comfort Network® (CCN) communicating controllers into BACnet MS/TP and Modbus networks.

The BACnet/Modbus Carrier Translator is a micro controller-based module that provides the ability to integrate Carrier CCN-based controllers into Modbus and BACnet networks. The BACnet/Modbus Carrier Translator (33CNTRAN485) provides CCN to Modbus Remote Terminal Unit (RTU) and BACnet Master-Slave/ Token-Passing (MS/TP) protocol conversion.

The Carrier Translator can be mounted in the controls section of any CCN equipment and converts CCNbased controller data to BACnet or Modbus. The Carrier Translator is outdoor duty rated and contains CCN RS-485 and BACnet/Modbus communications connectors.

When connected to a CCN controller, the BACnet/Modbus Carrier Translator allows a third party BACnet or Modbus device to read and write to the CCN controller’s mapped status display, time schedule, and setpoint schedule data. Note that status display write access is subject to the CCN equipment controller’s defined read/write access for each status display item.

  • 3-wire removable BACnet/Modbus connector
  • 3-wire fixed screw terminal CCN connector
  • 2-wire fixed screw terminal Power connector
  • Red Processor Status LED
  • Yellow CCN Communication Status LED
  • Green BACnet/Modbus Communication Status LED
Power Requirements 3 VA @ 24 Vac + 25%
Dimensions 2.1 in H x 5 in W x 4 in D
(53.3 mm x 127 mm x 101.6 mm)
Operating Temperature -40°F to 158°F
(-40°C to 70°C)
Storage Temperature -40°F to 185°F
(-40°C to 85°C)
Operating Humidity 0 to 95%, non-condensing
CCN Communications 9600, 19.2K, 38.4K baud
BACnet MS/TP Communications EIA-485
at 9600, 19.2K, 38.4K baud
Modbus RTU Communications EIA-485
at 9600, 19.2K, 38.4K baud
  Data Bits 8
  Parity Odd, Even, None
  Stop Bits 0,1,2
  Flow Control None, XON/XOFF

Conforms to guidelines for radiated and conducted emissions for a Class A device as stated in FCC Rules and Regulations Part 15, Subpart J.

  • 3-wire removable BACnet/Modbus connector
  • 3-wire fixed screw terminal CCN connector
  • 2-wire fixed screw terminal Power connector
  • Red Processor Status LED
  • Yellow CCN Communication Status LED
  • Green BACnet/Modbus Communication Status LED
Power Requirements 3 VA @ 24 Vac + 25%
Dimensions 2.1 in H x 5 in W x 4 in D
(53.3 mm x 127 mm x 101.6 mm)
Operating Temperature -40°F to 158°F
(-40°C to 70°C)
Storage Temperature -40°F to 185°F
(-40°C to 85°C)
Operating Humidity 0 to 95%, non-condensing
CCN Communications 9600, 19.2K, 38.4K baud
BACnet MS/TP Communications EIA-485
at 9600, 19.2K, 38.4K baud
Modbus RTU Communications EIA-485
at 9600, 19.2K, 38.4K baud
  Data Bits 8
  Parity Odd, Even, None
  Stop Bits 0,1,2
  Flow Control None, XON/XOFF

Conforms to guidelines for radiated and conducted emissions for a Class A device as stated in FCC Rules and Regulations Part 15, Subpart J.