ZS Outdoor Air Sensors
ZS-OA
Temperature Only, Temperature Plus Humidity
The Carrier ZS line of communicating outdoor air sensors are designed to measure the air temperature and/or humidity outdoors. Designed for outdoor mounting, the UV-resistant plastic shield keeps the sensor out of the sunlight and allows for excellent air circulation. These outdoor sensors have etched Teflon® lead wires and can withstand high humidity and condensation environments. They are made to perform in a wide range of temperature and moisture conditions.
The ZS outdoor air sensors connect directly to the dedicated sensor network (Rnet) of a Carrier i-Vu controller. This communicating sensor network supports up to 15 ZS sensors through a single port, eliminating the need to consume multiple inputs on the controller.
Averaging temperature sensor probe: Bendable aluminum / 3/16 in. diameter / Length of 8, 12, or 24 ft. specified at time of order
Sensing Element | ||
Temperature | Range: 20° to 120°F (-5° to 50°C)
Accuracy: ±0.36°F (0.2°C) |
|
Humidity | Range: 10% to 90%
Accuracy: Humidity is calibrated at 73°F (23°C) ±2.0% typical. Less than 0.5% drift per year. |
|
Sensor | ||
Temperature | Range: 20° to 120°F (-5° to 50°C)
Accuracy: ±0.9°F (0.5°C) |
|
Humidity | Range: 10% to 90%
Accuracy: Humidity is calibrated at 73°F (23°C). ±2.0% typical. Less than 0.5% drift per year. |
|
Enclosure Material | Polycarbonate, UL94V-0 | |
Enclosure Rating | NEMA 4, IP66, UV rated | |
Enclosure Dimensions | Width: 5 in. (12.7 cm)
Height: 4.15 in. (10.54 cm) Depth: 2.5 in. (6.35 cm) |
|
Probe | Temperature sensor probe: Vented polycarbonate shield, .5 in. (1.27 cm) OD 1.2 in. (3.05 cm)
Temperature/humidity sensor probe:ABS with SS filter 1.0 in. (2.5 cm) diameter 2.4 in. |
|
Sensing element shield | Vented polycarbonate shield
0.5 in. (1.27 cm) outside diameter 1.2 in. (3.05 cm) long with 1/2 in. NPT threads |
|
Power Requirements | 12 Vdc @ 6 mA | |
Power Supply | The 4-conductor Rnet cable from a controller supplies +12 Vdc @ 210 mA. For additional power, use an external power supply. Use the above power requirements to calculate the size of the external power supply. The controller and the external power supply must share a common ground. | |
Communication | 115 kbps | |
Environmental operating range | -40 to 158°F (-40 to 70°C) | |
Mounting | 3/16 in. holes | |
Listed by | FCC Part 15-Subpart B-Class B, CE |
Averaging temperature sensor probe: Bendable aluminum / 3/16 in. diameter / Length of 8, 12, or 24 ft. specified at time of order
Sensing Element | ||
Temperature | Range: 20° to 120°F (-5° to 50°C)
Accuracy: ±0.36°F (0.2°C) |
|
Humidity | Range: 10% to 90%
Accuracy: Humidity is calibrated at 73°F (23°C) ±2.0% typical. Less than 0.5% drift per year. |
|
Sensor | ||
Temperature | Range: 20° to 120°F (-5° to 50°C)
Accuracy: ±0.9°F (0.5°C) |
|
Humidity | Range: 10% to 90%
Accuracy: Humidity is calibrated at 73°F (23°C). ±2.0% typical. Less than 0.5% drift per year. |
|
Enclosure Material | Polycarbonate, UL94V-0 | |
Enclosure Rating | NEMA 4, IP66, UV rated | |
Enclosure Dimensions | Width: 5 in. (12.7 cm)
Height: 4.15 in. (10.54 cm) Depth: 2.5 in. (6.35 cm) |
|
Probe | Temperature sensor probe: Vented polycarbonate shield, .5 in. (1.27 cm) OD 1.2 in. (3.05 cm)
Temperature/humidity sensor probe:ABS with SS filter 1.0 in. (2.5 cm) diameter 2.4 in. |
|
Sensing element shield | Vented polycarbonate shield
0.5 in. (1.27 cm) outside diameter 1.2 in. (3.05 cm) long with 1/2 in. NPT threads |
|
Power Requirements | 12 Vdc @ 6 mA | |
Power Supply | The 4-conductor Rnet cable from a controller supplies +12 Vdc @ 210 mA. For additional power, use an external power supply. Use the above power requirements to calculate the size of the external power supply. The controller and the external power supply must share a common ground. | |
Communication | 115 kbps | |
Environmental operating range | -40 to 158°F (-40 to 70°C) | |
Mounting | 3/16 in. holes | |
Listed by | FCC Part 15-Subpart B-Class B, CE |