500-Ton Air Cooled Chiller
Model # 30XAA5006J-02N13
The air-cooled chiller cooling process involves the absorption of heat from process water and the heat is then transferred into the air. Air-cooled chillers are most commonly used in applications where space for the unit(s) is limited and the size of the discharged heat load is not a factor.
We inventory air-cooled chillers, ranging from 10 tons to 500 tons (applications down to 1 ton available).
Features
- Ready for outdoor operation with minimal setup
- Complete microprocessor control center
- Trailer-mounted
- Dual point power connection
- Pre-wired pump, 1200 gpm @ 100 ft-head
- Low ambient temperature operation to 0°F
- Brine mode to 25°F
- 300 psig water pressure option available
Carrier Rentals Equipment Line Up
We have a diverse and modern fleet of rental equipment and the expertise to apply them.
Looking for Equipment Specifications?
Download information for some of our most commonly rented equipment.
Mechanical Data
Water Connections | 6" 150 lb RF flange in/out |
Water Volume | 93 gallons |
Water Max. Pressure | 150 psig |
Minimum Load | 42 tons |
Min / Max Water Flow | 800 / 2004 gpm |
Circuits/Compressors | 2 / 3 |
Refrigerant/Charge | R134a / 205 / 415 / 415 lb |
Oil/Charge | POE / 7.5 / 6.3 / 7.5 gal. |
Electrical Data - Dual Disconnect, Pump
Voltage | 460V / 3 phase / 60 hertz |
Disconnect Size | 1000 amps / 1000 amps |
Connections | Leviton Series 16 Cam |
Cables Circuit 1 | 4/0 - (2) Per Ph, (1) Gnd |
Cables Circuit 2 | 4/0 - (3) Per Ph, (1) Gnd |
FLA/MCA Circuit 1 | 377 / 447 amps (w/pump) |
FLA/MCA Circuit 2 | 528 / 604 amps |
Rec. Service | 600 / 800 amps |
Shipping Data
Shipping Weight | 38,000 lbs (chiller) |
Trailer | 15,000 lbs |
Dimensions | 48’ L x 8’ W x 8 ½‘ H |
Leveling Required | Within 1” per 8' |
Installed Clearances | 10’ (sides), 4’ (electrical) |